Meshed system or a system with multiple sources require directional relays discussed in subsequent lectures.
The first step in the overcurrent protection is estimation of the fault current. If the system is radial and fed from a single or equivalent source, this job is simplified. For conservative calculation, utility source impedance should be considered as zero (unlimited MVA supplying capacity). The reason for this assumption is that, changes in utility system, addition of generators, strengthening of transmission network etc. can reduce the source impedance. Consequently, the maximum fault current is limited by the impedance of the distribution transformer. In a single source radial system, typically fault current reduces as we move away from the source (an exception being a system with large motor loads at the remote ends). The transformer short circuit current can be calculated from this formula, |