Module 4 : Overcurrent Protection
Lecture 14 : Fuse Protection
   Recap
   In this lecture we have learnt the following:
Available Fault Current: This is the maximum rms short circuit current that flows to a faulted node or point. The
  magnitude is limited by the ac impedance to that specific point. The impedance is the sum of the utility source impedance and the in-plant circuit impedance.
Continuous Current Rating: As with all overcurrent devices, most fuses are limited to a continuous loading of 80% of
  their label rating. This is due to the mutual heating between switch, fuse and adjacent devices.
Current limiting Fuse: First generation fuses, e.g. expulsion type, only limit the duration (time) of the fault. The modern
  current-limiting fuse, however, not only limits the duration of the fault, but also limits the magnitude of the fault.
Interrupting Rating: This is the maximum current that overcurrent device can safely interrupt at a stated voltage,
  frequency, and short circuit power factor. Interrupting ratings are expressed in rms symmetrical amperes. It is common for a device rated 200 000 A to have an abbreviated marking such as 200 KA IR.
Voltage Rating: The rms alternating current voltage at which the fuse is designed to operate. Fuses of the 600 V class
  will always function safely on a lesser voltage. For example 600 V fuses are typically used on 480 and 208 V.
  Congratulations, you have finished Lecture 14. To view the next lecture select it from the left hand side menu of the page