10.5.2 |
Single Line to Ground Fault (SLG): |
|
|
On an unloaded system (fig 10.7), let there be 'a' phase to ground fault with a fault impedance Zf. Then, the faulted system is described by,
Ia = If, Ib = 0 and Ic = 0. Applying sequence transformation, we get
Thus, I0 = I1 = I2 =Ia/3. Let Vf represent the voltage of the transmission line at the receiving end of the line where fault is created.
Further, from equation, |
| |
Equivalent in the sequence domain we get by premultiplying (9) by T -1
i.e. |