Module1 : Process Design of Heat Exchanger

Lecture 2 : Thermal Design Considerations

 

 

The flow rates of both hot and cold streams, their terminal temperatures and fluid properties are the primary inputs of thermal design of heat exchangers.

1.2. Thermal design considerations

Thermal design of a shell and tube heat exchanger typically includes the determination of heat transfer area, number of tubes, tube length and diameter, tube layout, number of shell and tube passes, type of heat exchanger (fixed tube sheet, removable tube bundle etc), tube pitch, number of baffles, its type and size, shell and tube side pressure drop etc.

1.2.1. Shell

Shell is the container for the shell fluid and the tube bundle is placed inside the shell. Shell diameter should be selected in such a way to give a close fit of the tube bundle. The clearance between the tube bundle and inner shell wall depends on the type of exchanger ( [2]; page 647) . Shells are usually fabricated from standard steel pipe with satisfactory corrosion allowance. The shell thickness of 3/8 inch for the shell ID of 12-24 inch can be satisfactorily used up to 300 psi of operating pressure.

1.2.2. Tube

Tube OD of ¾ and 1'' are very common to design a compact heat exchanger. The most efficient condition for heat transfer is to have the maximum number of tubes in the shell to increase turbulence. The tube thickness should be enough to withstand the internal pressure along with the adequate corrosion allowance. The tube thickness is expressed in terms of BWG (Birmingham Wire Gauge) and true outside diameter (OD). The tube length of 6, 8, 12, 16, 20 and 24 ft are preferably used. Longer tube reduces shell diameter at the expense of higher shell pressure drop. Finned tubes are also used when fluid with low heat transfer coefficient flows in the shell side. Stainless steel, admiralty brass, copper, bronze and alloys of copper-nickel are the commonly used tube materials.

1.2.3. Tube pitch, tube-layout and tube-count

Tube pitch is the shortest centre to centre distance between the adjacent tubes. The tubes are generally placed in square or triangular patterns (pitch) as shown in the Figure 1.5 . The widely used tube layouts are illustrated in Table 1.2.

The number of tubes that can be accommodated in a given shell ID is called tube count. The tube count depends on the factors like shell ID, OD of tube, tube pitch, tube layout, number of tube passes, type of heat exchanger and design pressure.

1.2.4. Tube passes

The number of passes is chosen to get the required tube side fluid velocity to obtain greater heat transfer co-efficient and also to reduce scale formation. The tube passes vary from 1 to 16. The tube passes of 1, 2 and 4 are common in application. The partition built into exchanger head known as partition plate (also called pass partition) is used to direct the tube side flow.