Chapter 8: Unsymmetrical Faults

Double- Line -to Ground Fault

The faulted segment for a 2LG fault is shown in Fig. 8.7 where it is assumed that the fault has occurred at node k of the network. In this the phases b and c got shorted through the impedance Zf to the ground. Since the system is unloaded before the occurrence of the fault we have the same condition as (8.8) for the phase-a current. Therefore

(8.17)

 

 

Fig. 8.7 Representation of 2LG fault.

Also voltages of phases b and c are given by

(8.18)

 

 

Therefore

(8.19)

 

 

 

We thus get the following two equations from (8.19)

(8.20)

 

(8.21)

 

 

Substituting (8.18) and (8.20) in (8.21) and rearranging we get

(8.22)

 

 

Also since I fa = 0 we have

(8.23)

 

 

The Thevenin equivalent circuit for 2LG fault is shown in Fig. 8.8. From this figure we get

(8.24)

 

 

 

The zero and negative sequence currents can be obtained using the current divider principle as



(8.25)

 

 

(8.26)

 

 

Fig. 8.8 Thevenin equivalent of a 2LG fault.

 

Example 8.3