Example 8.4
Consider the network shown in Fig. 8.10. The system parameters are given below
Generator G : 50 MVA, 20 kV, X" = X1 = X2 = 20%, X0 = 7.5% |
|
Motor M : 40 MVA, 20 kV, X" = X1 = X2 = 20%, X0 = 10%, Xn = 5% |
|
Transformer T1 : 50 MVA, 20 kV Δ /110 kVY, X = 10% |
|
Transformer T2 : 50 MVA, 20 kV Δ /110 kVY, X = 10% |
|
Transmission line: X1 = X2 = 24.2 Ω , X0 = 60.5 Ω |
|
We shall find the fault current for when a (a) 1LG, (b) LL and (c) 2LG fault occurs at bus-2.
Fig. 8.10 Radial power system of Example 8.4.
Let us choose a base in the circuit of the generator. Then the per unit impedances of the generator are:
The per unit impedances of the two transformers are
The MVA base of the motor is 40, while the base MVA of the total circuit is 50. Therefore the per unit impedances of the motor are
For the transmission line
Therefore
Let us neglect the phase shift associated with the Y/ Δ transformers. Then the positive, negative and zero sequence networks are as shown in Figs. 8.11-8.13.
Fig. 8.11 Positive sequence network of the power system of Fig. 8.10.
Fig. 8.12 Negative sequence network of the power system of Fig. 8.10.
Fig. 8.13 Zero sequence network of the power system of Fig. 8.10.
From Figs. 8.11 and 8.12 we get the following Ybus matrix for both positive and negative sequences
Inverting the above matrix we get the following Zbus matrix
Again from Fig. 8.13 we get the following Ybus matrix for the zero sequence
Inverting the above matrix we get
Hence for a fault in bus-2, we have the following Thevenin impedances
Alternatively we find from Figs. 8.11 and 8.12 that
(a) Single-Line-to-Ground Fault : Let a bolted 1LG fault occurs at bus-2 when the system is unloaded with bus voltages being 1.0 per unit. Then from (8.7) we get
per unit |
|
Also from (8.4) we get
per unit |
|
Also I fb = I fc = 0. From (8.5) we get the sequence components of the voltages as
Therefore the voltages at the faulted bus are
(b) Line-to-Line Fault : For a bolted LL fault, we can write from (8.16)
per unit |
|
Then the fault currents are
Finally the sequence components of bus-2 voltages are
Hence faulted bus voltages are
(c) Double-Line-to-Ground Fault : Let us assumes that a bolted 2LG fault occurs at bus-2. Then
Hence from (8.24) we get the positive sequence current as
per unit |
|
The zero and negative sequence currents are then computed from (8.25) and (8.26) as
per unit
per unit
|
|
Therefore the fault currents flowing in the line are
Furthermore the sequence components of bus-2 voltages are
Therefore voltages at the faulted bus are
|