Now, suppose, that a self clearing transient three phase short circuit fault occurs on the line. During the fault, the electrical output power drops to zero. The resulting rotor acceleration advances rotor angle to . After a time interval
, corresponding to angle , the fault is cleared and the operating point jumps back to the sinusoidal curve. As per equal area criteria, the rotor will swing up to maximum rotor angle
, such that,
Accelerating Area (A1) = Decelerating Area (A2)
Rotor angle corresponding to fault clearing time can be computed by swing equation, |
| |
where H is the equivalent rotor angle inertia.
During fault, Pe = 0, hence, |
| |
On integrating both the sides with respect to variable t, |
| |
Recall that prior to fault, is a stationary point. Hence, the initial condition of is specified as follows: |