Module 2 : Current and Voltage Transformers
Lecture 7 : CT Saturation and DC Offset Current
7.4

Cautions in CT Selection

 

While choosing a CT for a particular application, it is necessary to observe following precautions.

The CT rating and continuous load current should match. For example, if maximum load current is 90A, a 100:5 CT may
  be acceptable but 50:5 is not acceptable.
The maximum fault current should be less than 20 times the CT rated current. For example, 100:5 CT can be used, so
  long as burden on the CT is within the rated values and maximum primary fault current is below 2000A.
The voltage rating of CT should be compatible. For example, 100:5 C100 would give linear response, upto 20 times
  rated current provided CT burden is kept below(100/20 x 5 = 1). With 2 burden, this CT can be used only if maximum current is limited to 1000A.
Paralleling of CT's e.g. in differential protection, or with SLG fault can create significant errors in CT performance. One
  should generally ascertain that magnetizing current is kept much below the pick up value.
7.4.1 Exercise Problems
1. If the current ratio is adequate for a protection, but CT burden is high; then the performance of CT may deteriorate due to
 

large magnetizing current and/or saturation problem (see fig 7.9). The CT performance can be improved by connecting the CT's in series (see fig 7.10).

    

Show the dotted terminals for correct secondary series connection in fig 7.10.

What is the VA of CT in fig 7.9 and 7.10 respectively?

2. Mark the following statements as true or false:

Electromechanical relays tend to saturate at high currents. This reduces the relay burden on CT, and so that the CT

  performance at moderately high currents may be considered better than at relay's rated burden at 5A.  

Use of instantaneous over current relays has the potential to overcome this problem of saturation of CT's.

Differential protection can operate on external faults due to the unequal saturation of CT's.
 
10