Module 7: Energy conservation
  Lecture 22: Flow measuring devices
 
 
(Neglecting minor-loss)
(Minor–loss can be minimized by slowly or gradually expanding the diverging section. That is why, the venturimeters are long, bulky, and expensive)
(without loss)

For Venturimeters, or actual flowrate is calculated as,   where  is called the discharge coefficient and accounts for minor–loss or viscous–loss, because of non- uniform flow– patterns in the converging–diverging sections and at throat. The supplier of the instrument provides a plot to calculate :

 
(Fig. 22b)