Y- Δ Connected Transformer
The schematic diagram of a Y- Δ connected transformer is shown in Fig. 7.15. It is assumed that the Y-connected side is grounded with the impedance ZN . Even though the zero sequence current in the primary Y-connected side has a path to the ground, the zero sequence current flowing in the Δ -connected secondary winding has no path to flow in the line. Hence we have Ia0 = 0. However the circulating zero sequence current in the Δ winding magnetically balances the zero sequence current of the primary winding.
Fig. 7.15 Schematic diagram of a Y- Δ connected transformer.
The voltage in phase-a of both sides of the transformer is related by
Also we know that
We therefore have
|
(7.67) |
Separating zero, positive and negative sequence components we can write
|
(7.68) |
|
(7.69) |
|
(7.70) |
The positive sequence equivalent circuit is shown in Fig. 7.16 (a). The negative sequence circuit is the same as that of the positive sequence circuit except for the phase shift in the induced emf. This is shown in Fig. 7.16 (b). The zero sequence equivalent circuit is shown in Fig. 7.16 (c) where Z0 = Z + 3ZN . Note that the primary and the secondary sides are not connected and hence there is an open circuit between them. However since the zero sequence current flows through primary windings, a return path is provided through the ground. If however, the neutral in the primary side is not grounded, i.e., ZN = ∞ , then the zero sequence current cannot flow in the primary side as well. The sequence diagram is then as shown in Fig. 7.16 (d) where Z0 = Z .
Fig. 7.16 Sequence diagram of a Y- Δ connected transformer: (a) positive sequence, (b) negative sequence, (c) zero sequence with grounded Y-connection and (d) zero sequence with ungrounded Y-connection.
|